Using Auto False Echo Suppression; Level Application Example - Siemens Sitrans Probe LU Instruction Manual

Hide thumbs Also See for Sitrans Probe LU:
Table of Contents

Advertisement

Oxley Creek WWTP Water Reclamation
(Probe LU Manual) Vendor Manual
Calibration – steps 1 to 7
1.
Open the menu
(Click on
parameters.)
2.
Enter the new value for Low Calibration Point (default units are meters).
3.
Enter the corresponding value for Low Level Point in percent (default is 0).
4.
Enter the new value for High Calibration Point (default units are meters).
5.
Enter the corresponding value for High Level Point in percent (default is 100).
6.
Click on
7.
SITRANS Probe LU is now ready to operate.

Using Auto False Echo Suppression

If SITRANS Probe LU displays a false high level, or the reading is fluctuating between the
correct level and a false high level, you can use the Auto False Echo Suppression
parameters to prevent false echo detection. See

Level application example

The Primary Value (PV) can be level or volume
PV will be the same as the Secondary Value 1 (SV1). SV1 is the sum of level plus level
offset (if any).
Far Range
1.
For details, see
7ML19985JB02
.
Near
Range
High Level
Point = 100%
Level
Low Level
Point = 0%
Level Offset
(if any)
How the LTB works:
SITRANS Probe LU (PROFIBUS PA) – INSTRUCTION MANUAL
and select the button
to see the schematic showing the PROFIBUS
TVT setup
1
. If volume conversion is not selected, the
Sensor Offset
High
Calibration
Sensor Value
Point = 3 m
Secondary Value 1
on page 57.
Doc Id: VM11
Active Date: 15/12/2006
on page 93 for instructions.
Low
Calibration
Point = 5 m
Page 21