Article number
•
for logic links
•
for uprating
•
for redundant control of a load
Switching frequency
•
with resistive load, max.
•
with inductive load, max.
•
on lamp load, max.
Total current of the outputs
Current per module, max.
•
Cable length
•
shielded, max.
unshielded, max.
•
Interfaces
Number of PROFINET interfaces
Number of PROFIBUS interfaces
Number of USB interfaces
Number of DRIVE-CLiQ interfaces
1. Interface
Interface types
•
RJ 45 (Ethernet)
Number of ports
•
•
integrated switch
Protocols
IP protocol
•
•
PROFINET IO Controller
PROFINET IO Device
•
•
SIMATIC communication
•
Open IE communication
•
Web server
•
Media redundancy
PROFINET IO Controller
Services
–
PG/OP communication
–
Isochronous mode
Direct data exchange
–
–
shortest clock pulse
IRT
–
–
PROFIenergy
SIMATIC Drive Controller
Equipment Manual, 11/2022, A5E46600370-AC
6ES7615-4DF10-0AB0
Yes; For technological functions and high-speed outputs: No
No
Yes; For technological functions and high-speed outputs: No
35 kHz; With High Speed output, 1 kHz with standard output
2 Hz; Max. 1 J per channel
11 Hz
8 A
30 m
30 m
3
1
2; USB 3.0 (without function, no connection permissible)
4; DRIVE-CLiQ interfaces (24 V / 450 mA per interface for connecting
encoders/measuring systems)
Yes; X150
3
Yes
Yes; IPv4
Yes
Yes
Yes
Yes; Optionally also encrypted
Yes
Yes
Yes
Yes
Yes; Requirement: IRT and isochronous mode (MRPD optional)
500 µs
Yes
Yes; per user program
Technical specifications
6ES7615-7DF10-0AB0
250 µs
71