Technical specifications
Article number
UDP multicast
DHCP
DNS
SNMP
DCP
LLDP
Encryption
Web server
HTTP
HTTPS
OPC UA
Runtime license required
OPC UA Client
Application authentication
Security policies
User authentication
Number of connections, max.
Number of nodes of the client interfaces,
max.
Number of elements for one call of
OPC_UA_NodeGetHandleList/OPC_UA_R­
eadList/OPC_UA_WriteList, max.
Number of elements for one call of
OPC_UA_NameSpaceGetIndexList, max.
Number of elements for one call of
OPC_UA_MethodGetHandleList, max.
Number of simultaneous calls of the cli­
ent instructions per connection (except
OPC_UA_ReadList,OPC_UA_WriteList,
OPC_UA_MethodCall), max.
Number of simultaneous calls of the cli­
ent instructions
OPC_UA_ReadList,OPC_UA_WriteList and
OPC_UA_MethodCall, max.
Number of registerable nodes, max.
Number of registerable method calls of
OPC_UA_MethodCall, max.
Number of inputs/outputs when calling
OPC_UA_MethodCall, max.
OPC UA Server
Application authentication
76
6ES7615-4DF10-0AB0
Yes; 128 multicast circuits (of which max. 5 via X150)
Yes
Yes
Yes; disconnected by default
Yes
Yes
Yes; Optional
 
Yes; Standard and user pages
Yes; Standard and user pages
 
Yes; "Small" license required
Yes; Data Access (registered Read/Write), Method Call
Yes
Available security policies: None, Basic128Rsa15, Basic256Rsa15,
Basic256Sha256
"anonymous" or by user name & password
40
5 000
300
20
100
1
5
5 000
100
20
Yes; Data Access (Read, Write, Subscribe), Method Call, Alarms &
Condition (A&C), Custom Address Space
Yes
6ES7615-7DF10-0AB0
 
 
Yes; "Large" license required
SIMATIC Drive Controller
Equipment Manual, 11/2022, A5E46600370-AC