Technical specifications
Article number
Isolation
Isolation tested with
Degree and class of protection
IP degree of protection
Standards, approvals, certificates
CE mark
UKCA mark
cULus
RCM (formerly C-TICK)
KC approval
EAC (formerly Gost-R)
Suitable for safety functions
Highest safety class achievable in safety mode
Performance level according to ISO 13849-1
•
•
SIL acc. to IEC 61508
Probability of failure (for service life of 20 years
and repair time of 100 hours)
–
Low demand mode: PFDavg in accord
ance with SIL2
–
Low demand mode: PFDavg in accord
ance with SIL3
–
High demand/continuous mode: PFH in
accordance with SIL2
High demand/continuous mode: PFH in
–
accordance with SIL3
Ambient conditions
Ambient temperature during operation
•
min.
•
max.
Ambient temperature during
storage/transportation
•
min.
max.
•
Altitude during operation relating to sea level
•
Installation altitude above sea level, max.
•
Ambient air temperature-barometric pres
sure-altitude
configuration / header
configuration / programming / header
Programming language
80
6ES7615-4DF10-0AB0
707 V DC (type test)
IP20 control cabinet installation / open type
Yes
Yes
Yes
Yes
Yes
Yes
Yes; e.g. emergency stop, acknowledgment button
PLd (PLe if exclusively F-CPU is used)
SIL 2 (SIL 3 if exclusively F-CPU is used)
< 14.00E-04
< 2.00E-05 PLd (if exclusively F-CPU is used)
< 14.00E-09
if exclusively F-CPU is used: < 1.00E-09 (at a site altitude of up to
3000 m); < 2.00E-09 (at a site altitude of more than 3000 m and up
to 4000 m)
0 °C
55 °C
-40 °C; Long-term storage: -25 °C
70 °C; Long-term storage: +55 °C
4 000 m; as of an altitude of 2000 m, the maximum ambient air tem
perature is reduced by 7 °C per 1000 m; see SINAMICS documenta
tion for SINAMICS S120 drive components
Permissible air pressure: 620 hPa ... 1 060 hPa
6ES7615-7DF10-0AB0
SIMATIC Drive Controller
Equipment Manual, 11/2022, A5E46600370-AC