Chapter 2: Mount And Install The Smart-Hopping 2.0 Access Point 1.4 Ghz; Access Point Placement Guidelines - Philips Smart-hopping 2.0 Installation Manual

Access point 1.4 ghz
Table of Contents

Advertisement

Chapter 2: Mount and Install the Smart-hopping 2.0 Access Point 1.4 GHz

Access Point Placement Guidelines

Note the following important guidelines when locating Smart-hopping Access Points:
Consider building construction when placing Access Points to account for interference
from ceramic wall tile, lead lined walls, elevator shafts, reinforced windows, and other
obstacles which may cause signal degradation.
Place Access Points in locations where there is no more than one wall between the
Access Point and the coverage area.
Ensure that the coverage area takes into account bathrooms, hallways, and windows.
Access Point (internal) antennas must be more than four inches (10 cm) away from
metal structures. If the antennas are too close to the structure, antenna performance
can be degraded.
Access Points or Remote Antennas shall not be placed closer than three feet (1 m) from
other Access Points or RAs to prevent signal overload conditions.
Each Smart-hopping Access Point requires a 100Mbps/Full Duplex or 1000 Mbps
switch port connection.
The coaxial cable bundle cable length may vary from 69 - 79 feet. When planning
remote antenna placement, ensure the maximum length between the Access Point
and the remote antenna is 69 feet.
Try to avoid placing Access Points close to other electrical devices (exit lights, light
fixtures, speakers, etc.). Devices like florescent light ballasts can create a significant
amount of interference that can impact system performance.
When installing a Smart-hopping network, Philips requires that the following LAN
cables are Shielded Twisted Pair cables:
Warning Qualified personnel must mount Access Points and use certified conductors and follow
national and local electrical codes.
All Smart-hopping devices are intended for indoor use only.
2-2
Cables connecting the switch to the Access Point Controllers
Cables connecting the switch to the Synchronization Units (that connects to the
Access Points)
DRAFT - 03 JUN 2022 13:32

Advertisement

Table of Contents
loading

This manual is also suitable for:

867216