Other Systems - Huawei FusionModule1000A20 Maintenance Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A20:
Table of Contents

Advertisement

FusionModule1000A20 Prefabricated All-in-One
Data Center
Maintenance Guide
Device
Smoke
detector
Heat
detector

4.3.4 Other Systems

Table 4-6 Monthly maintenance checklist for other systems
Maintenanc
Instructions
e Item
Pre-fab.
Check the exterior of
Module
the prefab. module
repainting
for damage or
corrosion.
Pre-fab.
Check whether there
module
are potential hazards
external
or pollutants around
environment
the prefab. modules.
Check whether there
is noticeable rubbish
around the prefab.
modules.
Issue 03 (2022-12-15)
Operation
Check the smoke
detector
indicator.
Check the heat
detector
indicator.
Criteria
The prefab.
module and
bases are free
from paint
flake-off, rust,
and corrosion.
There are no
potential
hazards or
pollutants
around the
prefab. modules.
There is no
noticeable
rubbish around
the prefab.
modules.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Check Standard
Maintenance Guide
The indicator
Replace the smoke
blinks once every
detector.
6s.
The indicator
Replace the heat detector.
blinks once every
6s.
Troubleshooting
Maintain or replace the rusty, corroded,
or damaged part.
Take measures to handle potential
hazards.
Clean the rubbish.
4 Routine Maintenance
42