5.3 Troubleshooting the Intelligent Heat Exchanger

Table 5-3 Troubleshooting the Intelligent Heat Exchanger
Symptom
Alarm
The
None
intelligent
heat
exchanger
has a black
screen of
death and
cannot be
started.
Issue 03 (2022-12-15)
Possible
Cause
There is
refrigerant
leakage.
Possible
Cause
The
intelligent
heat
exchanger
fails to start
because the
DC power
supply is
abnormal.
The
intelligent
heat
exchanger
fails to start
because the
mainboard
is faulty.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Common Faults and Troubleshooting Measures
Solution
Identify the leakage point of the pipeline. Drain the
refrigerant, and weld the leaking point. Then, charge
nitrogen into the pipeline, preserve the pressure to
verify the air tightness, vacuumize the pipeline, and
then fill refrigerant.
Solution
● If a group of intelligent heat exchangers fails to
start, possibly the upstream power supply is
abnormal. Check the cable connections between
the upstream power cabinet and the intelligent
heat exchangers.
● If a single intelligent heat exchanger fails to start,
check whether the corresponding circuit breaker
in the power cabinet has tripped. If not, check
whether the power cabinet works properly. If the
circuit breaker does not trip and the power
cabinet works properly, check the cable
connections to the intelligent heat exchanger.
● If the power supply is normal, the mainboard
may be burnt. If so, replace the equipment with a
new one.
1. Check whether the cables are securely connected.
2. Replace the equipment with a new one.
69