Huawei FusionModule1000A20 Maintenance Manual page 71

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A20:
Table of Contents

Advertisement

FusionModule1000A20 Prefabricated All-in-One
Data Center
Maintenance Guide
Symptom
Alarm
Manual
Operation
ATS
Communicat
ion Failed
Issue 03 (2022-12-15)
Possible
Cause
The ATS is
in manual
mode.
ATS
communicat
ion fails.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Common Faults and Troubleshooting Measures
Solution
cables from the ATS and label the cables. 5)
Remove the faulty ATS. 6) Install the new ATS. 7)
Reinstall the cables and tighten the screws. 8)
Reinstall the ATS controller by following
Reinstall the protective panel for the PDF. 10)
Turn on the upstream and downstream switches
of the PDF. 11) Check that the new ATS works
properly.
1. Check whether the ATS handle is inserted into the
ATS and whether the control mode switching
lever on the ATS is in the Manual position. If not,
press the AUTO button on the ATS controller so
that the AUTO indicator becomes steady green.
2. If the AUTO indicator is not steady green after
you press the AUTO button, check whether the
spring in the opening for the handle on the ATS is
stuck. If not, power off the equipment, remove
the ATS cover, and check whether cables are
connected properly and whether the position
switch is normal. Replace the position switch if it
is abnormal.
1. Check whether the indicators and display of the
ATS controller are normal.
2. Check whether the communications cable
between the ATS and the ECC is properly
connected, whether the wire sequence is correct,
and whether the cable is damaged. Rectify any
fault.
3. If all the preceding items are normal, power on
the equipment again and check whether the
alarm is cleared.
4. If the alarm persists, the ATS controller is faulty.
Replace the 8D controller by following
1
to 5. 9)
1
to 5.