Test Input Function - Panasonic WUME-SF4D-2 Instruction Manual

Safety light curtain type 4
Table of Contents

Advertisement

3-4 Test Input Function (Common for all cables)
The test input function is used to check the operation of the control output (OSSD 1 / 2).
This function forcibly turn OFF the control output (OSSD 1 / 2) when the device is in the light
receiving state. ON or OFF can be selected for the test input function using the test / reset input
wire (pink).
● Line synchronization
Light received /
Light blocked
Light received state
Light blocked state
During test input, the control output (OSSD 1 / 2) turns OFF.
The device can be reset to normal operation by connecting the test / reset input wire (pink) to
0V or +V (open in the case of manual reset).
<Timing chart>
Open
Test / Reset input
Shorted
Control output
(OSSD 1 / 2)
Notes: 1) The range depends on the number of beam channels and number of series connections.
2) Operation in auto reset mode is indicated. In manual reset mode, light is emitted when open and
stopped when short-circuited.
● Optical synchronization
Light received / Light blocked
Light received state
Light blocked state
During test input, the control output (OSSD 1 / 2) turns OFF.
The device can be reset to normal operation by open-circuiting the test / reset input wire (pink).
<Timing chart>
Open
Test / Reset input
Shorted
Control output
(OSSD 1 / 2)
Note: The range depends on the number of beam channels and number of series connections.
Do not use the test input function for the purpose of stopping the machine for which the device is
installed. Risk of death or serious injury.
© Panasonic Industrial Devices SUNX Co., Ltd. 2016
Interlock
Test / Reset input wire (Pink)
function
Manual reset
When using PNP output: Connect to +V
When using NPN output: Connect to 0V
Auto reset
When using PNP output: Connect to +V
When using NPN output: Connect to 0V
10 to 60ms (Note 1)
ON
OFF
Test / Reset input wire (Pink)
When using PNP output: Connect to +V
When using NPN output: Connect to 0V
10 to 60ms (Note)
ON
OFF
Open
Open
Open
WARNING
Functions
Control output (OSSD
Test input
1 / 2) state
Invalid
ON
Valid
OFF
Valid
OFF
Invalid
ON
OFF
70ms or less (Note 1)
Control output (OSSD
Test input
1 / 2) state
Invalid
ON
Valid
OFF
OFF
70ms or less (Note)
103