Table 10-1 CMU common alarms and troubleshooting measures
Alarm
Alarm
ID
Name
3800
Water
Alarm
3801
Door
Status
Alarm
Issue 08 (2022-11-15)
Major alarm: The device is faulty or the external environment is abnormal. As
a result, the output power decreases or the device stops feeding to the grid.
Minor alarm: Some components of the device are faulty but the device can
still connect to the grid and generate power.
Warning: The device functions normally, but its output power decreases or
some authorization functions fail due to external factors.
NO TE
[HVAC-No] indicates the number of the air conditioner.
Severity
Possible Cause
Major
Cause ID = 1
Water is detected in the
battery cabin.
Cause ID = 2
Water is detected in the
control unit cabin.
Major
Cause ID = 1–6
Battery compartment
door 1–6 is open.
Cause ID = 7
Battery compartment
door is open.
Copyright © Huawei Technologies Co., Ltd.
10

Alarm Reference

Suggestion
1. Check whether there is water in
the cabin. If yes, drain the water.
2. Check whether the devices in the
cabin are intact and normal. If yes,
manually clear the alarm. If not,
replace the damaged devices.
1. Check whether the cabin doors
are completely closed. If not, close
the doors completely.
2. Check whether the cable is
disconnected from the door status
sensor. If yes, connect the cable
correctly.
3. Check whether the door status
sensor is displaced. If yes, move it
back to the original position.
10 Alarm Reference