Huawei LUNA2000-2.0MWH Series User Manual page 217

Smart string ess
Hide thumbs Also See for LUNA2000-2.0MWH Series:
Table of Contents

Advertisement

LUNA2000-2.0MWH Series Smart String ESS
User Manual
Alarm
Alarm
ID
Name
3059
Communi
cation
Interrupti
on
Between
the Rack
Controller
and PCS
3060
Incompati
ble ESM
Issue 08 (2022-11-15)
Severity
Possible Cause
Major
Cause ID = 1
1. The
communications cable
between the CMU and
SmartLogger is
abnormal.
2. The
communications cable
between the PCS and
SmartLogger is
abnormal.
Major
Cause ID = 1
The replacement ESM
is incompatible with
the system.
Copyright © Huawei Technologies Co., Ltd.
10 Alarm Reference
Suggestion
1. Check whether the CMU status
indicator on the WebUI indicates
that the CMU is offline. If yes, check
whether the communications link
between the CMU and the
SmartLogger is normal.
2. Check whether the PCS status
indicator on the WebUI indicates
that the PCS is offline. If yes, check
whether the power supply to the
PCS is normal. If the power supply is
normal, issue a shutdown command
to the PCS, turn off the circuit
breaker on the AC side, and check
whether the communication link
between the PCS and the
SmartLogger is normal.
If the link is normal:
a. Determine the positions of the
input and output circuit breakers
associated with [ESC-No] and the AC
input power switch of the PSU.
b. Issue a hibernation command to
all ESRs, and turn off the switch on
the battery side, the switch on the
bus side, and the AC input power
switch of the PSU. Then wait for 5
minutes.
c. Turn on the AC input power switch
of the PSU, the switch on the battery
side, and the switch on the bus side
in sequence, and issue a running
command.
d. If the alarm persists, contact your
dealer or technical support.
1. The model of [ESR-CabinetNo
ESM-SlotNo] is incompatible with
the system. Replace it with an ESM
of the original model.
2. If the alarm persists, contact your
dealer or technical support.
207