LUNA2000-2.0MWH Series Smart String ESS
User Manual
11.1 (Optional) How to Level the ESS When Doors
Cannot Be Opened or Closed
Step 1 Use a jack to support the ESS.
●
●
Step 2 Adjust the height using leveling washers from the control unit cabin.
Scenario 1: The Upper Part of the Lock Tongue Interferes With the Upper Surface
of the Lock Base
Use leveling washers to raise ESS by 5–10 mm on the foundation under the door
hinge.
Issue 08 (2022-11-15)
NO TE
This procedure applies only to some models.
Jack specification: 30 t
Position requirements: on the control unit cabin side or its opposite side (the
short side of the ESS container).
NO TE
Wood sleepers can be used in the following circumstances.
● Insufficient jack height: Place wood sleepers underneath the jack.
● Earth ground: Use wood sleepers to extend contact area.
NO TE
The raising height leveling washers may vary according to the actual conditions.