Alarm
Alarm
ID
Name
3034
Rack
Controller
Cable
Connectio
n
Abnormal
Issue 08 (2022-11-15)
Severity
Possible Cause
Major
Cause ID = 1
The cable connection
between the battery
rack and the
corresponding power
module is incorrect.
Cause ID = 2
The power-on self-test
was terminated due to
a system exception.
Copyright © Huawei Technologies Co., Ltd.
10 Alarm Reference
Suggestion
If the system is in the array topology
identification process, wait until the
process is complete or exit the
process.
1. Locate the input and output
circuit breakers associated with
[ESC-No].
2. Issue a shutdown command, turn
off the switch on the battery side,
the switch on the bus side, and
the AC power supply switch, and
wait for 5 minutes.
3. Check whether the cable
connection between battery rack
and power module under [ESR-
CabinetNo] is correct by referring
to the DCDC replacement section
in the maintenance manual of
the product.
4. Check whether the auxiliary
power supply of battery rack
[ESR-CabinetNo] is normal and
whether the auxiliary power
supply switch is turned on by
referring to the product
maintenance manual.
5. Check that the power cable is
securely connected. Turn on the
AC power supply switch, the
switch on the battery side, and
the switch on the bus side in
sequence, and issue a startup
command.
6. If the alarm persists, contact your
dealer or technical support.
1. Check other active alarms of the
device and rectify the faults based
on the alarm handling
suggestions.
2. If the alarm persists after the
system is reset, contact your
dealer or technical support.