8.1.12. Object 0x605A: Quick stop option code
This object shall indicate what action is performed when the quick stop function is
executed.
The slow down ramp is the deceleration value of the used mode of operations.
-32768 to -1
+9 to +32 767
*Not supported these values. Do not set these values. If set the value 5-8, the drive slow
down ramp and transit into Switch On Disabled.
Value
No function
0
Disable drive function
+1
Slow down on slow down ramp and transit into Switch On Disabled
+2
Slow down on quick stop ramp and transit into Switch On Disabled
+3
Do not set
+4
Slow down on voltage limit and transit into Switch On Disabled
+5*
Slow down on slow down ramp and stay in Quick Stop Active
+6*
Slow down on quick stop ramp and stay in Quick Stop Active
+7*
Do not set
+8*
Slow down on voltage limit and stay in Quick Stop Active
Reserved
Definition
- 49 -