7.1.15. fe35:0x2E35, fe36: 0x2E36, fe37: 0x2E37 (Monitoring
of the analog input)
VF-MB1/S15
VIA input value: "Communication Number fe35"
VIB input value: "Communication Number fe36"
VIC input value: "Communication Number fe37"
These monitors can also be used as A/D converters irrespective of the inverter's control.
VIA / VIC input value monitor is capable of reading the data from external devices in a range of 0.00 to
100.00% (unsigned data: 0x0000 to 0x2710).
VIB input value monitor is capable of reading the data from external devices in a range of -100.00 to
100.00% (signed data: 0xD8F0 to 0x2710).
If analog input mode is selected with the frequency setting mode selection parameter, however, keep in
mind that any data entered via an analog terminal is regarded as a frequency command.
VF-AS3
RR input value: "Communication Number fe35"
RX input value: "Communication Number fe36"
II input value: "Communication Number fe37"
These monitors can also be used as A/D converters irrespective of the inverter's control.
RR / II input value monitor is capable of reading the data from external devices in a range of 0.00 to
100.00% (unsigned data: 0x0000 to 0x2710).
RX input value monitor is capable of reading the data from external devices in a range of -100.00 to
100.00% (signed data: 0xD8F0 to 0x2710).
If analog input mode is selected with the frequency setting mode selection parameter, however, keep in
mind that any data entered via an analog terminal is regarded as a frequency command.

7.1.16. fe14 : 0x2E14 (Cumulative run time)

The operated cumulative time is read by the hexadecimal number.
For example, when cumulative operation time is 18 hours, 0x12 (18 hours) is read.
0x12 (Hex.) = 18 (Dec., hour)
7.1.17. fe40 :0x2E40 (Analog output (FM)), fe41 :0x2E41 (AM
output monitor) (Only for the VF-AS3)
The output value of FM/AM terminal is read.
The value range is set to 0 to 10000 (0x2710).
For example, when FM/AM output value is 50.00%, 0x1388 (Hex.) is read.
0x1388 (Hex) = 50.00 (Dec %)
* If the parameter f681 (Analog output) is set to 0, FM output monitor cannot be used.
Please set 1 or 2 to f681 .
- 37 -