Wiring The Power Source - Sharp JW-20FL5 User Manual

Fl-net module (board)
Table of Contents

Advertisement

(2) Wiring the power source

When a 10BASE5 is used, 12 VDC power should be supplied to the transceiver.
Supply power to the 12 VDC power supply input terminal using a commercial constant voltage power
supply unit.
Item
Supply voltage
Current capacity
* Fuse (0.6 A)
12 VDC
* Use a fuse melt with time lag
(Accessory: Connector, cable length 1.5 m)
Remarks
- Use a power supply that is dedicated for use by the JW-20FL5.
- Do not reverse the positive and negative connections to the power terminals. Reversing the polarity
may damage the JW-20FL5.
Specifications
12 VDC –5%
0.5 A minimum.
12 VDC power supply input terminal
Black wire (-)
Red wire (+)
Twisted pair wires
Case
Cable
6-3
Chapter 6: Connection/Wiring
JW - 20FL5
LN TX RX 12V
T PE HE
S7 S6 S5 S4 S3 S2 S1 S0
ON
OFF
FG
RESET
Green wire
(ground)
S
H
I
E
L
D