DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
3.9

Network Communication

Firmware revision 2.10 or greater is required for network communication.
The control panel can be configured to communicate over an Ethernet network. Reports can be sent
over this network from the control panel to the ARC receiver. Remote programming can also be
conducted over this network. A DX4020 Network Interface Module (NIM) is required for network
communication. See Network Interface Module (DX4020) on page 36 for installation/configuration
instructions.
Use the following steps to configure the control panel for network communication:
1. Enter an IP address for the ARC receiver [refer to IP Address 1 (2) for Destination 1 (2)].
2. Set the Alternate Communications Options parameter to "5" (refer to page 102).
3. Set the Network Interface Module Options parameter to "3" (refer to page 105).
IP Address 1 (2) for Destination 1 (2)
Address:
IP Address 1, Destination 1: 0000 to 0031
-
IP Address 2, Destination 1: 0032 to 0063
-
IP Address 1, Destination 2: 0066 to 0097
-
IP Address 2, Destination 2: 0098 to 0129
-
Default: All zeroes (0)
Selections: 000.000.000.000 to 255.255.255.255
Each routing destination can be configured as a phone number or an IP address. When entering an IP
address, only the first 12 digits are used. For example, to enter an IP address of 172.30.1.101 into the
Phone 1, Destination 1 addresses, enter the following digits in the first 12 addresses: 1, 7, 2, 0, 3, 0,
0, 0, 1, 1, 0, 1.
See Table 39 for entry selections.
Table 39:
IP Address Entry Selections
Digit
Enter at
Keypad
1
[1]
2
[2]
3
[3]
4
[4]
5
[5]
Remote Programming Callback Number
Address: 0181 to 0212
Default: All zeroes (0)
Selections: 000.000.000.000 to 255.255.255.255 (see Table 39)
An IP address can be used to begin a remote programming session. See IP Address 1 (2) for
Destination 1 (2) to enter an IP address. See Remote Programming Call Back Number on page 55 for
more information.
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
Digit
Enter at Keypad
6
[6]
7
[7]
8
[8]
9
[9]
0
[0] or [1][0]
EN | 101