Table 51: Terminal Descriptions - Bosch DS7200V2-EXP Installation Manual

Table of Contents

Advertisement

DS7200V2-EXP | Installation Guide | 4. Reference Materials
Table 51:
Terminal Descriptions
Terminal
Silkscreen Label
1,2
18 VAC
3
Earth Ground Symbol
4
Data, Grn (Green)
5
Data, Yel (Yellow)
6,7
Aux Power 12 VDC (-)
8,9
Aux Power 12 VDC (+)
Aux/Data (RYGB)
Batt +
Batt -
10
PO 4
11
PO 3
12
PO 2
13
ALRM +
14
PO 1, A
15
PO 1, B
16
SMK +
17
18
Com
19
20
21
Com
22
23
24
Com
25
26
27
Com
28
29
30
31
32
PO 1 SELECT
Auxiliary
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
18 V, 50 VA; from transformer.
Earth ground.
Data Bus data on Terminal 4. Control panel supports up to 305 m (1000 ft) of 0.8 mm
(#22 AWG) wire on these terminals (any configuration).
Data Bus data on Terminal 5. Control panel supports up to 305 m (1000 ft) of 0.8 mm
(#22 AWG) wire on these terminals (any configuration).
Terminals 6 and 7 are auxiliary power. 1.2 A. Include any programmable outputs (PO 1
to PO 4) not configured for alarm output. Self-resetting overcurrent protection.
Terminals 8 and 9 are auxiliary power. 1.2 A. Include any programmable outputs (PO 1
to PO 4) not configured for alarm output. Self-resetting overcurrent protection.
4-pin connector to Data Bus and auxiliary power. Use to connect an Installer Keypad for
keypad programming.
Battery (+) spade. (red wire)
Battery (-) spade. (black wire)
Programmable Output 4, up to 500 mA (-). Include in Aux Power calculations for all
except "Alarm" output functions. Self-resetting overcurrent protection.
Programmable Output 3, up to 500 mA (-). Include in Aux Power calculations for all
except "Alarm" output functions. Self-resetting overcurrent protection.
Programmable Output 2. 500 mA (-).Include in Aux Power calculations for all except
"Alarm" output functions. Supervised for Horn/Speaker alarm function. Self-resetting
overcurrent protection.
Alarm power. Up to 1850 mA. Self-resetting overcurrent protection. Provides power for
supervised siren driver (PO 2) and Alarm Output (PO 1, A).
Jumper sets PO 1 terminals A (14) and B (15) for "dry" Form "A" contact or for Alarm
Output (using PO 1, A as negative (-) terminal).
Jumper sets PO 1 terminals A (14) and B (15) for "dry" Form "A" contact or for Alarm
Output (using PO 1, A as negative (-) terminal).
Not used.
L-1
Sensor Loop 1. Wire length for Sensor Loops 1 to 8 are limited only by the resistance
on the loop and potential EMI problems. Resistance must be < 100 with EOL resistor
shorted and detection devices connected.
Common for Sensor Loops 1 and 2.
L-2
Sensor Loop 2 input.
L-3
Sensor Loop 3.
Common for Sensor Loops 3 and 4.
L-4
Sensor Loop 4.
L-5
Sensor Loop 5.
Common for Sensor Loops 5 and 6.
L-6
Sensor Loop 6.
L-7
Sensor Loop 7.
Common for Sensor Loops 7 and 8.
L-8
Sensor Loop 8.
T
Connections for incoming phone line.
T1
Connections for premises devices such as telephones.
R1
Connections for premises devices such as telephones.
R
Connections for incoming phone line.
Configures PO 1 for Form "A" relay or Alarm Output.
Auxiliary Module and/or Program Key (PK32) 8-pin connector.
Description
EN | 130