Table 29: Ds7446Kp Keypad Icon Functions - Bosch DS7200V2-EXP Installation Manual

Table of Contents

Advertisement

DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
Enable Area Display (DS7446KP Keypad): If this option is enabled, the DS7446KP Keypad shows
the current state of each area using its four Area icons.
Table 29:
DS7446KP Keypad Icon Functions
Function
Icon flashes fast
Icon is On
Steady
Icon flashes slow
Icon is Off
If the "Enable Area Display" option is disabled, the DS7446KP Keypad displays the area to which it
is currently assigned if it is not in its home area. If the keypad moved to another area, the icon for
the new area lights steady. For example, if the keypad moved ([#][5][0]) to Area 1, no area icons
are lit. If it moved to Area 2, the Area 2 icon turns on.
Don't Show Zone Status on Keypads: If the "Don't Show Zone Status on Keypads" option is not
enabled in the Keypad # Options parameter, the text keypad displays "OK for All On" or "OK for
Perimeter Only" across the second line. This indicates that all zones are normal and the system is
ready to arm All On or Perimeter Only. If a controlled zone is faulted, the Area Idle Text for this
zone's assigned area replaces the "OK for All On/OK for Perimeter Only" message.
If a zone not configured for Perimeter Only arming is faulted, "OK for Perimeter Only" replaces
"OK for All On" on the text keypad's display. The system might be armed Perimeter Only, but
cannot be armed All On until the faulted zone is restored.
If the "Don't Show Zone Status on Keypads" option is enabled, the area idle text displays
continuously on line two when the keypad is idle.
LED keypads do not show zone status if this option is selected.
If the "Don't Show Zone Status on Keypads" option is selected, the default Area Idle Text
("Not Ready") should be changed. See Text Entry Addresses on page 47 for text entry
instructions.
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
Condition
Area is in alarm
Area is in armed, but not in alarm
Trouble condition exists, or zone is bypassed in area
Area is disarmed, no alarm/trouble conditions exist, no zones are
bypassed
EN | 73