Panel-Wide Parameters; Table 22: Phone Number Entry Selections - Bosch DS7200V2-EXP Installation Manual

Table of Contents

Advertisement

DS7200V2-EXP | Installation Guide | 3. Control Panel
Programming
3.2

Panel-Wide Parameters

3.2.1
Routing Destinations
The control panel has two routing destinations for the routing of reports. The control panel routes by
zone and report group to the destinations. For example, you can send alarm reports for one zone to
Destination 1 and for another zone to Destination 2. You can program two phone numbers (or IP
addresses) for each destination.
Communication Fail events are by destinations and not by phone number or IP address.
For a description of the routing/dialing process, see Communication Attempt Tables on page 123.
Phone Number 1 (2) for Destination 1 (2)
Address Range:
Phone 1, Destination 1: 0000 to 0031
-
Phone 2, Destination 1: 0032 to 0063
-
Phone 1, Destination 2: 0066 to 0097
-
Phone 2, Destination 2: 0098 to 0129
-
Default: All zeroes (0)
Selections: 0 to 14 (see Table 22)
Table 22:
Phone Number Entry Selections
Digit to be Dialed
1
2
3
4
5
6
7
8
When entering phone numbers, use "10" ([1][0] from the keypad) to dial "0"; enter "0" to
terminate the phone number. This does not apply when entering an IP address.
Terminate telephone numbers with less than 32 digits by entering a zero (0) in the
Address after the last digit to be dialed.
The control panel can dial up to 32 digits per phone number. Each digit occupies one address. If fewer
than 32 digits are entered into the Phone Number Address range, the control panel dials digits until it
reaches a terminator (0).
IP addresses can be entered into these addresses for network communication. See Network
Communication on page 101 for more information. Firmware revision 2.10 or greater is required for
network communication.
See Area # Account Number on page 65 for instructions on entering an account number.
Bosch Security Systems, Inc. | 04/12 | F01U253045-02
Enter at Keypad
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
Digit to be Dialed
9
0
*
#
P (4-second pause)
F (on-hook, pause, off-
hook)
Reserved
T (Terminate)
Enter at Keypad
[9]
[1][0]
[1][1]
[1][2]
[1][3]
[1][4]
[1][5]
[0]
EN | 50