Procedure
1.
Remove the front bezel. The fan assemblies will then be visible.
2.
Identify the fan to be replaced.
Fans are labeled on the chassis, and are numbered 1 and 2, with fan 1
on the left and fan 2 on the right. Refer to the fan status LEDs on front
panel of the server (behind the bezel) to see which fan has failed. In the
following figure, number 1 indicates the status LED for fan 1 (the left-
side fan), and number 2 indicates the status LED for fan 2 (the right-side
fan).
Item
1
2
3.
Remove the faulty fan by loosening the thumbscrews (turning them
counter-clockwise) until they are loose, then pulling the fan unit straight
out of the chassis. (The fan lead connector disengages automatically as
you remove the fan assembly.)
Figure 6-3 Fan assembly - G2 models 3080 and 3090
Replacing server components
Hitachi NAS Platform 3080/3090 G2 Hardware Reference Guide
Figure 6-2 Fan status LEDs
Description
Fan 1 status LED
Fan 2 status LED
63