Heating control - Extended settings

Options:
This parameter enables additional functions and communication objects, e.g. "Basic stage
heating".
Pos: 31.7.15 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/ModuleGrundstufe Heizen @ 40\mod_1421679979210_15.docx @ 312558 @ 3 @ 1
11.3.12

Basic stage heating

Note
Only available when the "Extended settings" parameter under "Heating control" is
set on "Yes".
Pos: 31.7.16 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/ModuleGrundstufe Heizen — Statusobjekt Heizen @ 40\mod_1421680039317_15.docx @ 312573 @ 3 @ 1
11.3.13

Basic stage heating - Status object heating

Options:
This parameter enables the "Status heating" communication object.
Pos: 31.7.17 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/ModuleGrundstufe Heizen — Wirksinn der Stellgröße @ 40\mod_1421680138767_15.docx @ 312588 @ 3 @ 1
11.3.14

Basic stage heating - Mode of the control value

Options:
The mode of the control value can be used to adapt the control value to de-energised opened
(normal) or de-energised closed (inverse) valves.
Normal: Value 0 means "Valve closed".
Inverse: Value 0 means "Valve open".
Pos: 31.7.18 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/ModuleGrundstufe Heizen — Hysterese (x 0,1°C) @ 40\mod_1421680196846_15.docx @ 312603 @ 3 @ 1
11.3.15
Basic stage heating - Hysteresis (x 0.1°C)
Options:
The hysteresis of the two-point controller specifies the fluctuation range of the controller around
the setpoint value. The lower switching point is located at "Setpoint value minus hysteresis" and
the upper point is at "Setpoint value plus hysteresis".
Note
This parameter is only available when the "Control value type" parameter is set
either on "2-point 1 Bit, Off/On" or "2-point 1 Byte, 0/100%".
KNX Technical Reference Manual | 1473-1-8681
Description of applications /
No
Yes
No
Yes
Normal
Inverse
Setting option between 3 - 255
objects
— 35 —