Temperature Reading - Cyclic Sending Of The Actual Temperature (Min); Temperature Reading - Difference Of Value For Sending The Actual Temperature (X 0.1°C); Temperature Reading - Adjustment Value For Internal Temperature Measurement (X 0.1°C); Temperature Reading - Monitoring Time For Temperature Reading (0 = No Monitoring) (Min) - ABB -i-Bus-KNX Millenium Reference Manual

Room temperature controller
Hide thumbs Also See for ABB-i-Bus-KNX Millenium:
Table of Contents

Advertisement

KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
Pos: 31.7.120 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — zyklisches Senden der aktuellen Ist-Temperatur (min) @ 40\mod_1421745118320_15.docx @ 313889 @ 3 @ 1
11.3.97

Temperature reading - Cyclic sending of the actual temperature (min)

Options:
The current actual temperature used by the device can be cyclically transmitted to the bus.
Pos: 31.7.121 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — Wertdifferenz für das Senden der Ist-Temperatur (x 0,1°C) @ 40\mod_1421745172686_15.docx @ 313904 @ 3 @ 1
11.3.98
Temperature reading - Difference of value for sending the actual temperature (x 0.1°C)
Options:
If the change in temperature exceeds the parameterized difference between the measured
actual temperature and the previous actual temperature that was sent, the changed value will
be transmitted.
Pos: 31.7.122 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — Abgleichwert für interne Temperaturmessung (x 0,1°C) @ 40\mod_1421745232216_15.docx @ 313919 @ 3 @ 1
11.3.99
Temperature reading - Adjustment value for internal temperature measurement (x 0.1°C)
Options:
Every installation location has different physical conditions (interior or exterior wall, lightweight
or solid wall, etc.). In order to use the actual temperature at the installation location as a
measured value for the device, a temperature measurement must be performed by an external
equalised and / or calibrated thermometer at the installation location. The difference between
the actual temperature displayed on the device and the actual temperature determined by the
external measurement device must be entered in the parameter field as an "Adjustment value".
Note
Pos: 31.7.123 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — Überwachungszeit Temperaturerfassung (0 = keine Überwachung) (min) @ 40\mod_1421745300966_15.docx @ 313934 @ 3 @ 1

11.3.100 Temperature reading - Monitoring time for temperature reading (0 = no monitoring) (min)

Options:
If no temperature is read within the parameterized time period, the device switches to error
mode. It transmits a telegram to the bus via the "Actual temperature error" object and applies
the operating mode and control value for error (0 - 255) settings.
Pos: 31.7.124 /Systemmodule/++++++++++++++ Seitenumbruch +++++++++++++++ @ 41\mod_1422789416992_0.docx @ 333487 @ @ 1
KNX Technical Reference Manual | 1473-1-8681
Setting option between 5 - 240
Setting option between 1 - 100
Setting option between 1 - 100
The calibration measurement should not be carried out immediately after the
device has been installed. The device should first adjust to the ambient
temperature before calibration is carried out. The calibration measurement
should be repeated shortly before or after the room is occupied.
This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Internal measurement" or "Weighted measurement".
Setting option between 0 - 120
Description of applications /
objects
— 62 —