11.3.113 Fan Coil Settings - Fan Speed Levels - Level Status Evaluation; 11.3.114 Fan Coil Settings Heating; 11.3.115 Fan Coil Settings For Heating - Speed Level 1 To 5 Up To Control Value (0 To 255) Heating; 11.3.116 Fan Coil Settings For Heating - Fan Speed Level Limit Heating For Eco Mode - ABB -i-Bus-KNX Millenium Reference Manual

Room temperature controller
Hide thumbs Also See for ABB-i-Bus-KNX Millenium:
Table of Contents

Advertisement

KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
Pos: 31.7.139 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Fancoil Einstellungen - Lüfterstufen — Auswertung Stufenstatus @ 40\mod_1421746389750_15.docx @ 314129 @ 3 @ 1

11.3.113 Fan coil settings - Fan speed levels - Level status evaluation

Options:
The controller obtains the current fan speed level for controlling a fan coil actuator either by
calculating it from the table of level values under "Fan coil settings for heating" or "Fan coil
settings for cooling", or by receiving feedback from the fan coil actuator. If the "Yes" option is
selected, the "Fan coil step status" object is activated for receiving the fan speed level from the
fan coil actuator.
Pos: 31.7.140 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Fancoil Einstellungen Heizen @ 40\mod_1421746450029_15.docx @ 314144 @ 3 @ 1

11.3.114 Fan coil settings heating

Note
This parameter is only available if the "Device function" parameter is set on either
"Single device" or "Master device" and the "Control value type" parameter is set
on "Fan coil". In addition, the "Control function" parameter must be set on either
"Heating", "Heating with additional stage", "Heating and cooling" or "Heating and
cooling with additional stages".
Pos: 31.7.141 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Fancoil Einstellungen Heizen — Lüfterstufe 1- 5 bis Stellgröße (0 - 255) Heizen @ 40\mod_1421746567638_15.docx @ 314159 @ 3 @ 1

11.3.115 Fan coil settings for heating - Speed level 1 to 5 up to control value (0 to 255) heating

Options:
In this parameter, the control values of the controller are assigned to fan speed levels. This
assignment is used if the fan speed levels are transmitted together with the control values.
Note
Pos: 31.7.142 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Fancoil Einstellungen Heizen — Lüfterstufenbegrenzung Heizen bei Ecobetrieb @ 40\mod_1421746645592_15.docx @ 314174 @ 3 @ 1

11.3.116 Fan coil settings for heating - Fan speed level limit heating for eco mode

Options:
This parameter limits the fan speed level when the system is switched to eco mode.
Pos: 31.7.143 /Systemmodule/++++++++++++++ Seitenumbruch +++++++++++++++ @ 41\mod_1422789416992_0.docx @ 333487 @ @ 1
KNX Technical Reference Manual | 1473-1-8681
No
Yes
Setting option between 0 - 255
These level settings should be adjusted to match the settings in the fan coil
actuator.
Setting the "Control value type" to "Fan coil" in the control parameters is only
useful for one of either the basic stage or the additional stage. Setting the
basic and additional stage parameters to fan coil is not useful, since the
control of only one fan coil actuator each for heating and cooling is supported.
The "Fan speed level 4 - 5 up to control value (0 - 255) heating" parameters
are available only when the "Number of fan speed levels" is set on "5 levels".
No
Yes
Description of applications /
objects
— 66 —