Delay; Min/Max Value Transducer - ABB -i-Bus-KNX Millenium Reference Manual

Room temperature controller
Hide thumbs Also See for ABB-i-Bus-KNX Millenium:
Table of Contents

Advertisement

KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
Pos: 31.35 /Layout bis 2014-11-11/Online-Dokumentation (+KNX)/Überschriften (--> Für alle Dokumente <--)/3. Ebene/U - Z/Verzögerung @ 41\mod_1422541098275_15.docx @ 331620 @ 2 @ 1
11.8.6

Delay

Pos: 31.36 /Layout bis 2014-11-11/Online-Hilfe/Power-Tool/Power-Tool 2/chm-Online-Hilfe/App/Verzoegerung/App. - Verzögerung - DIN-A4 @ 9\mod_1269508848356_15.docx @ 53088 @ @ 1
Telegrams can be received via the "Input" object using the "Delay" application. The telegrams received are sent
out on the "Output" object with a set delay time.
The object types for "Input" and "Output" can be collectively parameterised for different applications.
Delay objects
No.
Object name
0
Input (1 Bit)
0
Input (1 Bit)
0
Input (1 Bit)
0
Input (1 Byte 0..100 %)
0
Input (1 Byte 0..255)
0
Input (2 Byte Float)
0
Input (2 Byte Signed)
0
Input (2 Byte Unsigned)
0
Input (4 Byte Float)
0
Input (4 Byte Signed)
0
Input (4 Byte Unsigned)
1
Output (1 Bit)
1
Output (1 Bit)
1
Output (1 Bit)
1
Output (1 Byte 0..100 %)
1
Output (1 Byte 0..255)
1
Output (2 Byte Float)
1
Output (2 Byte Signed)
1
Output (2 Byte Unsigned)
1
Output (4 Byte Float)
1
Output (4 Byte Signed)
1
Output (4 Byte Unsigned)
2
Delay time (2 Byte)
Pos: 31.37 /Layout bis 2014-11-11/Online-Dokumentation (+KNX)/Überschriften (--> Für alle Dokumente <--)/3. Ebene/M - O/Min- / Maxwertgeber @ 41\mod_1422541161503_15.docx @ 331637 @ 2 @ 1
11.8.7

Min/Max value transducer

Pos: 31.38 /Layout bis 2014-11-11/Online-Hilfe/Power-Tool/Power-Tool 2/chm-Online-Hilfe/App/MinMax/App. - Min- / Maxwertgeber - DIN-A4 @ 10\mod_1269512210610_15.docx @ 53189 @ @ 1
Up to eight input values can be compared with each other using the "Min/max value transducer" application. The
application can output the highest input value, the smallest input value or the average of all input values on the
output.
The size of the input objects, and with it also the size of the output object can be adapted for the most diverse
applications. You can select from the following object types:
1-byte 0..100 %, for comparison of percent values
1-byte 0..255, for the comparison of decimal values between 0 and 255
2-byte float, for the comparison of 2-byte floating point values (physical values such as temperature,
brightness value etc.)
2-byte signed, for the comparison of decimal values between -32,768 and +32,767
2-byte unsigned, for the comparison of decimal values between 0 and 65,535
4-byte float, for the comparison of 4-byte floating point values (physical values such as acceleration, electrical
current, work etc.)
4-byte signed, for the comparison of decimal values between -2,147,483,648 and 2,147,483,647
4-byte unsigned, for the comparison of decimal values between 0 and 4,294,967,295
Hint:
With whole numbers the average value is rounded.
KNX Technical Reference Manual | 1473-1-8681
Description of applications /
Data type
1 Bit EIS1 / DPT 1.001
1 Bit EIS7 / DPT 1.008
1 Bit EIS7 / DPT 1.007
1 Byte EIS6 / DPT 5.001
1 Byte EIS14 / DPT 5.010
2 Byte EIS5 / DPT 9.xxx
2 Byte EIS10 / DPT 8.001
2 Byte EIS10 / DPT 7.001
4 Byte EIS9 / DPT 14.xxx
4 Byte EIS11 / DPT 13.001
4 Byte EIS11 / DPT 12.001
1 Bit EIS1 / DPT 1.001
1 Bit EIS7 / DPT 1.008
1 Bit EIS7 / DPT 1.007
1 Byte EIS6 / DPT 5.001
1 Byte EIS14 / DPT 5.010
2 Byte EIS5 / DPT 9.xxx
2 Byte EIS10 / DPT 7.001
2 Byte EIS10 / DPT 7.001
4 Byte EIS9 / DPT 14.xxx
4 Byte EIS11 / DPT 13.001
4 Byte EIS11 / DPT 12.001
2 Byte EIS10 / DPT 7.001
objects
Flags
C, W
C, W
C, W
C, W
C, W
C, W
C, W
C, W
C, W
C, W
C, W
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, T
C, R, W