Application "1-Button Light Scene Extension Unit With Memory Function - ABB -i-Bus-KNX Millenium Reference Manual

Room temperature controller
Hide thumbs Also See for ABB-i-Bus-KNX Millenium:
Table of Contents

Advertisement

KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
Objects
No.
Object name
0
Switching (rising edge) (1 bit)
Switching (rising edge) (1-byte 0..100%)
Switching (rising edge) (1-byte 0..255)
Switching (rising edge) (2-byte float)
Switching (rising edge) (2-byte signed)
Switching (rising edge) (2-byte unsigned)
Switching (rising edge) (4-byte float)
Switching (rising edge) (4-byte signed)
Switching (rising edge) (4-byte unsigned)
1
Switching (falling edge) (1 bit)
Switching (falling edge) (1-byte 0..100%)
Switching (falling edge) (1-byte 0..255)
Switching (falling edge) (2-byte float)
Switching (falling edge) (2-byte signed)
Switching (falling edge) (2-byte unsigned)
Switching (falling edge) (4-byte float)
Switching (falling edge) (4-byte signed)
Switching (falling edge) (4-byte unsigned)
Pos: 31.20 /Layout bis 2014-11-11/Online-Dokumentation (+KNX)/Applikations- / Objektbeschreibungen/KNX/KNX-Sensorik/Millenium/6125-26-29-IR - Bedienelement/Applikationen "Bedienelement mit Multifunktion"/Applikation "1-Tasten-Lichtszenennebenstelle mit Speicherfunktion" @ 41\mod_1422540212387_15.docx @ 331481 @ 2 @ 1
11.7.5

Application "1-button light scene extension unit with memory function"

When a button is actuated a predefined light scene number is called up. In each case, the application makes a
separate set of parameters and communication objects available for the 1st and the 2nd button. The application
makes it possible to call up a light scene via one button side while the other button side can be assigned with a
further "button-oriented" function. The user has the option to trigger a light scene memory command via a long
actuation of the button.
Parameters
General parameter
Duration of long operation (s)
Storage function light scenes
Number of light scene
Objects
No.
Object name
0
Number of light scene
KNX Technical Reference Manual | 1473-1-8681
Settings
Time input from 0.3 to 10.0 seconds
• deactivated
• activated
1 ... 64
Description of applications /
Data type
1 Bit EIS1 / DPT 1.001
1 Byte EIS6 / DPT 5.001
1 Byte EIS14 / DPT 5.010
2 Byte EIS5 / DPT 9.xxx
2 Byte EIS10 / DPT 7.001
2 Byte EIS10 / DPT 8.001
4 Byte EIS9 / DPT 14.xxx
4 Byte EIS11 / DPT 13.001
4 Byte EIS11 / DPT 12.001
1 Bit EIS1 / DPT 1.001
1 Byte EIS6 / DPT 5.001
1 Byte EIS14 / DPT 5.010
2 Byte EIS5 / DPT 9.xxx
2 Byte EIS10 / DPT 7.001
2 Byte EIS10 / DPT 8.001
4 Byte EIS9 / DPT 14.xxx
4 Byte EIS11 / DPT 13.001
4 Byte EIS11 / DPT 12.001
Comments
Only available when parameter "Storage
function light scenes" is set on "activated".
Data type
1 Byte EIS6 / DPT 18.001
objects
Flags
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
C, W ,T ,U
Flags
C, T
— 94 —

Advertisement

Table of Contents
loading

Table of Contents