Temperature Reading - Inputs Of Weighted Temperature Reading; Temperature Reading - Weighting Of Internal Measurement (0 To 100%); Temperature Reading - Weighting Of External Measurement (0 To 100%); Temperature Reading - Weighting Of External Measurement 2 (0 To 100%) - ABB -i-Bus-KNX Millenium Reference Manual

Room temperature controller
Hide thumbs Also See for ABB-i-Bus-KNX Millenium:
Table of Contents

Advertisement

KNX Technical Reference Manual
®
ABB-i-Bus
-KNX Millenium
Pos: 31.7.115 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — Eingänge der gewichteten Temperaturerfassung @ 40\mod_1421744775118_15.docx @ 313829 @ 3 @ 1
11.3.93

Temperature reading - Inputs of weighted temperature reading

Options:
Specifies the temperature reading inputs for the weighted measurement, in which the calculated
weighted average of the inputs is used as an input value for control
Note
This parameter is only available when the "Inputs of temperature reading"
parameter is set on "Weighted measurement".
Pos: 31.7.116 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — Gewichtung der internen Messung (0..100%) @ 40\mod_1421744843727_15.docx @ 313844 @ 3 @ 1
11.3.94

Temperature reading - Weighting of internal measurement (0 to 100%)

Options:
Specifies the weighting of the internal measurement at a level between 0% and 100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "Internal and external measurement" or "Internal and
2x external measurement".
Pos: 31.7.117 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — Gewichtung der externen Messung (0..100%) @ 40\mod_1421744895847_15.docx @ 313859 @ 3 @ 1
11.3.95

Temperature reading - Weighting of external measurement (0 to 100%)

Options:
Specifies the weighting of the external measurement at a level between 0% and 100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "Internal and external measurement","2x external
measurement" or "Internal and 2x external measurement".
Pos: 31.7.118 /DinA-4 -- Online/Applikations- / Parameterbeschreibungen -- (KNX)/Applikation/Objekt-RTR/Module/Temperaturerfassung — Gewichtung der externen Messung 2 (0..100%) @ 40\mod_1421745031552_15.docx @ 313874 @ 3 @ 1
11.3.96

Temperature reading - Weighting of external measurement 2 (0 to 100%)

Options:
Specifies the weighting of the external measurement 2 at a level between 0% and 100%. When
added together with the (0%...100%) weighting of the external measurement, the result must be
100%.
Note
This parameter is only available when the "Inputs of weighted temperature
reading" parameter is set on "2x external measurement" or "Internal and 2x
external measurement".
Pos: 31.7.119 /Systemmodule/++++++++++++++ Seitenumbruch +++++++++++++++ @ 41\mod_1422789416992_0.docx @ 333487 @ @ 1
KNX Technical Reference Manual | 1473-1-8681
Description of applications /
Internal and external measurement
2 x external measurement
Internal and 2x external measurement
Setting option between 0 - 15
Setting option between 0 - 15
Setting option between 0 - 15
objects