Note: The set value is the percentage of FU2-33 [Rated
Motor Current].
Output Current
FU1-57
[OLT Level]
FU1-57
[OLT Level]
Output Frequency
[Overload Trip Operation]
Related Functions:
FU2-33 [Rated Motor Current]

FU1-59: Stall Prevention Mode Selection (Bit set)

FU1-60: Stall Prevention Level

FU1? Stall prev.
59
000
Factory Default:
000
This bit set parameter follows the conventions used in
I/O-15 and I/O-16 to show the ON (bit set) status.
FU1? Stall level
60
180 %
Factory Default:
180 %
This function is used to prevent the motor from stalling
by reducing the inverter output frequency until the motor
current decreases below the stall prevention level. This
function can be selected for each mode of acceleration,
steady speed, and deceleration via bit combination.
Note: The set value is the percentage of FU2-33 [Rated
Motor Current].
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Time
FU1- 58 [OLT Time]
Overload Trip
Time
59
000
000
60
180
180
97
Chapter 6 - Parameter Description [FU1]
FU1-59 [Stall Prevention Mode Selection]
Setting Range
FU1-59
3
bit 2
bit 1
bit
rd
nd
st
0
0
1
001
0
1
0
010
1
0
0
100
When FU1-59 is set to ' 111' , stall prevention works during
accelerating, steady speed and decelerating.
Note: The acceleration and deceleration time may take
longer than the time set in DRV-01, DRV-02 when Stall
Prevention is selected.
Note: If stall prevention status persists, inverter may stop
during acceleration.
Related Functions:
FU2-33 [Rated Motor Current]
Output Current
FU1-60
[Stall Level]
FU1-60
[Stall level]
Output Frequency
[Stall Prevention during Acceleration]
Output Current
FU1-60
[Stall Level]
FU1-60
[Stall Level]
Output Frequency
[Stall Prevention during Steady Speed]
Description
Stall Prevention during
Acceleration
Stall Prevention during Steady
Speed
Stall Prevention during
Deceleration
Time
Time
Time
Time