Output Frequency
Output Voltage
ON
FX-CM
[[Stop Mode: ' Free-run' ]

FU1-08: DC Injection Braking Frequency

FU1-09: DC Injection Braking On-delay Time

FU1-10: DC Injection Braking Voltage

FU1-11: DC Injection Braking Time

FU1? DcBr freq
08
5.00 Hz
Factory Default:
5.00 Hz
FU1? DcBlk time
09
0.10 sec
Factory Default:
0.10 sec
FU1? DcBr value
10
50 %
Factory Default:
50 %
FU1?
DcBr time
11
1.0 sec
Factory Default:
1.0 sec
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Output Cutoff
Time
Output Cutoff
Time
Stop Command
Time
08
5.00
5.00
09
0.10
0.10
10
50
50
11
1.0
1.0
Chapter 6 - Parameter Description [FU1]
By introducing a DC voltage to the motor windings this
function stops the motor immediately. Selecting ' DC-
Brake' in FU1-07 activates FU1-08 through FU1-11.
FU1-08 [DC Injection Braking Frequency] is the
frequency at which the inverter starts to output DC
voltage during deceleration.
FU1-09 [DC Injection Braking On-delay Time] is the
inverter output blocking time before DC injection braking.
FU1-10 [DC Injection Braking Voltage] is the DC voltage
applied to the motor and is based on FU2-33 [Rated
Current of Motor].
FU1-11 [DC Injection Braking Time] is the time the DC
current is applied to the motor.
Output Frequency
FU1-08
[DCBr Freq]
Output Voltage
FU1-10
[DCBr Value]
ON
FX-CM
[DC Injection Braking Operation]
89
Time
t1: FU1-09
t2: FU1-11
Time
t1
t2
Stop Command
Time