FU1-12: Starting DC Injection Braking Time
FU1-13: Staring DC Injection Braking Time
FU1?
DcSt value
12
50 %
Factory Default:
50 %
FU1?
DcSt time
13
0.0 sec
Factory Default:
0.0 sec
Inverter holds the starting frequency for Starting DC
Injection Braking Time. It outputs DC voltage to the
motor for FU1-13 [Starting DC Injection Braking Time]
with the FU1-12 [Starting DC Injection Braking Voltage]
before accelerating.
Output Frequency
FU1-22
Output Voltage
FU1-12
t1: FU1-13 [Starting DC Injection
t1
Braking Time]
Output Current
Run Command
FX-CM
[Starting DC Injection Braking Operation]
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
12
50
50
13
0.0
0.0
Time
Time
Time
ON
Time
Related Functions:
FU2-33 [Rated Current of Motor]
n
FU2-33: the DC current is limited by this parameter.
Note: The DC injection braking function does not function
when either FU1-12 or FU1-13 is set to "0".
Note: FU1-12 [Starting DC Injection Braking Voltage] is
also used as the DC Injection Braking Voltage for the
multifunction input when the multifunction input is set to
"DC braking".

FU1-14: Pre-excitation Time

FU1?
PreExTime
14
1.0 sec
Factory Default:
1.0 sec
When you set ON to the operation command (FWD,
REV), the inverter conducts pre-exciting automatically
for the time specified by this parameter.
l After FU1-14 [Pre-excitation Time] elapses the
inverter starts normal operation in the following
graph.
Code
LCD display
FU1-14
PreExTime
Output freq
[Hz]
Output
voltage
[V]
FX-CM
Related function:
FU2-34 [No Load Motor Current (RMS)]
FU1-16 [Pre-excitation Current ]
90
14
1.0
1.0
Factory setting
Setting range
1 [sec]
0 ~ 60 [sec]
T1 = Pre-excitation time