Ul Marking - LG SV-iS5 Instruction Manual

Variable frequency drives
Hide thumbs Also See for SV-iS5:
Table of Contents

Advertisement

(9) UL Marking

1. Short Circuit Rating
"Suitable For Use On A Circuit Capable Of Delivering Not More Than Table1 RMS Symmetrical
Amperes, 240V for 240V rated inverters, 480V for 480V rated inverters Volts Maximum,"
Table 1. RMS Symmetrical Amperes for iS5 series.
SV008iS5-2, SV008iS5-4, SV015iS5-2, SV015iS5-4, SV022iS5-2, SV022iS5-4,
SV037iS5-2, SV037iS5-4,SV055iS5-2, SV055iS5-4, SV075iS5-2, SV075iS5-4,
SV110iS5-2, SV110iS5-4, SV150iS5-2, SV150iS5-4,SV185iS5-2, SV185iS5-4,
SV220iS5-2, SV220iS5-4, SV3005iS5-2, SV300iS5-4, SV370iS5-2, SV370iS5-4
SV450iS5-2, SV450iS5-4, SV550iS5-2, SV550iS5-4, SV750iS5-4,
2. OVERLOAD PROTECTION
IOLT: IOLT(inverter Overload Trip) protection is activated at 150% of the inverter rated current for
1 minute and greater.
OLT : Inverter shuts off its output when inverter output current exceeds its overload trip level for
overload trip time. OLT is selected when FU1-56 is set to "Yes" and activated at 120% of FU1-57
[Motor rated current] for 60 sec set in FU1-58.
3. OVER SPEED PROTECTION
"Not Provided With Overspeed Protection".
4.Risk of Electric Shock
More than one disconnect switch may be required to de-energize the equipment before servicing.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Model
VI
Rating
5,000A
10,000A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents