Operation Using Control Terminals - LG SV-iS5 Instruction Manual

Variable frequency drives
Hide thumbs Also See for SV-iS5:
Table of Contents

Advertisement

4.2 Operation using Control Terminals

1. Install a potentiometer on terminals
V1, VR, 5G and connect wiring as
shown below.
P1 P2
P3 FX RX NC
JOG CM
CM BX
2. Apply AC power.
3. Confirm that the DRV 03 is set at
' Fx/Rx-1' .
4. LCD: Press [? ] key to move DRV 04.
7-Seg: Rotate encoder knob until ' 04'
is displayed.
5. LCD: Press [PROG] key.
7-Seg: Press [PROG/ENT] key.
6. LCD: Press [? ] key and set at ' V1' .
7-Seg: Rotate encoder knob and set
at ' 2' .
7. LCD: Press [ENT] key.
7-Seg: Press [PROG/ENT] key.
8. Press [SHIFT/ESC] key.
9. Set the frequency by rotating the
potentiometer.
10. Close the FX or RX contact to run the
motor.
11. Open the FX or RX contact to stop the
motor.
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
LCD Display
1 ㏀, 1/2 W
VR VI
RST
I
FM 5G
DRV?T/K
00
STP
DRV? Drive mode
03
Fx/Rx-1
DRV?
Freq mode
04
Keypad-1
DRV?
Freq mode
04
Keypad-1
DRV?
Freq mode
04
DRV?
Freq mode
04
DRV?T/V
00
STP
DRV?T/V
00
STP
The FWD or REV LED starts blinking.
The STOP/RESET LED starts blinking.
Chapter 4 – Quick start procedures
0.0 A
0.00Hz
The DRV LED is ON.
The PROG/ENT LED is turned ON.
V1
The PROG/ENT LED is turned ON.
V1
The PROG/ENT LED is turned OFF.
0.0 A
0.00Hz
0.0 A
60.00Hz
The RUN LED starts blinking.
The STOP/RESET LED starts blinking.
53
7-Segment Display

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents