Chapter 6 - Parameter Description [I/O]
[Ssearch]
AXA-AXC is CLOSED during the inverter is speed
searching.
[Step pulse]
When Auto (Sequence) operation is selected in I/O-50,
AXA-AXC outputs pulse signals on every step.
Related Functions:
I/O-50 ~ I/O-84 [Auto Operation]
Output Frequency
Sequence 1
Sequence 3
SEQ1 / 2F
SEQ2 / 2F
SEQ1 / 1F
SEQ3 / 2F
SEQ3 / 1F
P1-CM
ON
' SEQ-L'
P2-CM
' SEQ-M'
P3-CM
ON
ON
ON
' Go step'
AXA-AXC
ON
ON
ON
' Step pulse'
Minimum 100msec
[AXA-AXC configured as ' Step pulse' ]
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
Sequence 2
Time
Time
ON
Time
ON
ON
Time
ON
ON
Time
132
[Seq pulse]
When Auto (Sequence) operation is selected in I/O-50,
AXA-AXC outputs pulse signals on the last step.
Output Frequency
(Forward)
Seq# / 2F
1D
(Forward)
Seq# / 1F
Seq# / 3F
1T
1S
2T
AXA-AXC
' Step pulse'
[AXA-AXC configured as ' Step pulse' ]
[Ready]
AXA-AXC is CLOSED when the inverter is ready to run.
[Trv. ACC]
CLOSED when output frequency reaches Accel
frequency.
[Trv. DEC]
CLOSED when output frequency reaches Decel
frequency.
[MMC]
Automatically set to ' MMC' when ' MMC' is selected in
APP-01.
[Zspd Dect]
0 rpm detection signal in Vector Control
[Torq Dect]
Torque detection signal in Vector and Sensorless Vector
Control.
2D
Time
3D
(Reverse)
2S
3T
3S
DRV-02
ON
Time
Minimum 100msec