CHAPTER 6 -

6.1 Drive group [DRV]

DRV-00: Command Frequency or Command
Torque/ Output Current (LCD)
DRV? Cmd. Freq*
00
0.00 Hz
Factory Default:
0.00 Hz
* In Torque mode: LCD display - Cmd. Trq
7 Segment - r (Rpm)
l In FU2-39 [Control Mode Selection], 4
(Sensorless_T) 6 (Vector_TRQ) is torque mode.
l DRV-00 [Command Frequency or Command
Torque] has two functions.
1) Digital frequency setting
- When DRV-04 [Frequency or Torque Mode] is set to 0
(KeyPad-1) or 1 (KeyPad-2), command freq is not
settable above FU1-20 [Maximum Frequency].
2) Monitoring function setting
- Command frequency displayed during stop
- Output current/frequency displayed during run.
Analog/digital frequency command setting in DRV-04
[Frequency or Torque Mode]:
l DRV-04 [Frequency or Torque Mode] is set to 2
(V1),3 (I) or 4 (V1+I), frequency command is set via
I/O-01~10 [Analog Frequency command/Torque].
Refer to I/O-01~10 for detail description.
l DRV-16 [Speed Unit Selection] is set to 1 (Rpm),
speed is displayed in Rpm.
l If FU2-39 is set to 4 (Sensorless_T) or 6
(Vector_TRQ), speed is displayed as the percent
[%] to the rated torque. Torque command is
settable in DRV-04 [Frequency or Torque Mode].
* Factory default setting = 100[%]
Morek IT OÜ, Rauna 24, 76506 Saue Harjumaa, Estonia. www.morek.eu Tel. +372 604 1423 Fax +372 604 1447 morek@morek.eu
PARAMETER DESCRIPTION
F *
0.00
0.00
(Up to 150[%] settable)
l Setting the DRV-04 [Frequency or Torque Mode]
☞ Note: In torque mode, speed unit is automatically
displayed in [%].
Setti
Parameter
DRV-04
ng
Name
0
KeyPad-1
Digital freq.
command
1
KeyPad-2
2
V1
Analog
freq.
3
I
command
4
V1+I
l Command Freq/Torque setting via " V1" input
terminal when set DRV-04 [Frequency/Torque
mode] to 2 (V1) or 4 (V1+I)
Code
Default setting
I/O-01
10 [msec]
I/O-02
0 [V]
I/O-03
0 [Hz]
I/O-04
10 [V]
I/O-05
60 [Hz]
79
Programming Description
1. In DRV-00, press the [PROG]
key. 2. Enter the desired freq. 3.
Press the [ENT] key to write the
new value into memory.
1. In DRV-00, press the [PROG]
key. 2. Press the [ñ(Up)] or
[ò(Down)] key to set the desired
freq., while the inverter keeps
running. 3. Press the [ENT] key
to write the new value into
memory.
Control terminal "V1" Voltage
analog input (0 to 10V)
See the description of I/O-01~05.
Control terminal "I" Current
analog input (4 to 20mA)
See the description of I/O-06~10.
Control terminal "V1"+"I"
(0-10V/4-20mA) Analog input .
See the description of I/O-01~10.
Setting range
0 ~ 10000 [msec]
0 ~ 10 [V]
0 ~ Max. freq
0 ~ 10 [V]
0 ~ Max freq

Hide quick links: