The override functions calculate output frequency by the following expression:
Frequency command value × (1+
1) Additive override
In this mode, an externally input override frequency is added to operation frequency command.
[Ex.1: VIA (Reference frequency), VIC (Override input)] [Ex.2: VIB (Reference frequency), VIA (Override input)]
Output frequency
Override
(VIC input)
Ex.1:
f660 = 3 (VIC input), f661 = 0 (disabled)
Output frequency = Reference frequency + Override (VIC input [Hz])
Ex.2:
f660 = 1 (VIA input), f661 = 0 (disabled)
Output frequency = Reference frequency + Override (VIA input [Hz])
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Value [%] selected with
Over-ridden frequency
(
0
10V
)+Value [Hz] selected with f660
100
Output frequency
Forward run
Override
VIA input
)
(VI/II input)
(Reference
frequency)
-10V
F-117
Over-ridden frequency
(
0
10V
Reverse run
E6581611
VIB input
)
(Reference
6
frequency)