Toshiba VF-S15 Instruction Manual page 64

For 3-phase induction motors
Hide thumbs Also See for VF-S15:
Table of Contents

Advertisement

3.2.1
[Example of  setting procedure]
Panel operation
(1) Run and stop using the panel keypad (cmod=1)
Use the
●The direction of rotation is determined by the setting of parameter  (forward run, reverse run selection).
●Forward run and reverse run are switchable with the extension panel (option). Set the parameter fr
(2) RUN and STOP using external signals (cmod=0): Sink (Negative) logic
Use external signals to the inverter terminal block to start and stop the motor.
Short
F
Open
F
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
How to run and stop
LED display

MODE
auh
cmod
1
0
0cmod
RUN
STOP
and
keys on the panel keypad to start and stop the motor.
: Motor runs.
: Motor stops.
RUN
STOP
(: forward run, : reverse run)
(forward run, reverse run selection) to 2 or 3. (Refer to section 5.8)
and
terminals: run forward
CC
and
terminals: slow down and stop
CC
Displays the output frequency (operation stopped).
(When standard monitor display selection f710=0 [output frequency])
Displays the first basic parameter [History (auh)].
Turn the setting dial, and select "cmod".
Press the center of the setting dial to read the parameter value.
(Standard default: 1).
Turn the setting dial to change the parameter value to 0 (terminal block).
Press the center of the setting dial to save the changed parameter.
cmod and the parameter set value are displayed alternately.
Frequency
F-CC
C-5
Operation
Slow down
and stop
ON
OFF
E6581611
3