(3) Holding the output of signals in ON status
If the conditions for activating the functions assigned to RY-RC terminal and OUT terminal agree with and
as a result the output of signals is put in ON status, the output of signals is held ON, even if the conditions
change. (Output terminal holding function)
Assign function 80 to 83 to an input terminal.
Once RY-RC terminal or OUT terminal is turned on when the assigned input terminal is ON, RY-RC terminal
or OUT terminal is held ON.
Function No.
Each one of the following numbers (81, 83) is an inverse signal.
 Usage example ···operational signal, brake signal
Low-speed detection signal outputs the signal when the output frequency exceeds the setting of f100.
This signal can be used as an operation signal by setting f100 to 0.0Hz. (Default setting)
This signal can also be used as an electromagnetic brake excitation/release signal.
Setting example) When outputting the brake signal from RY-RC terminal
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Code
Holding of RY-RC terminal
80
HDRY
output
Holding of OUT-NO terminal
82
HDOUT
output
Title
Function
f100
Low-speed signal output frequency
f130
Output terminal selection 1A (RY-RC)
Output frequency
Setting frequency
Low-speed detection signal :
RY-RC terminals
Inversion of low-speed
detection signal
Function
ON : Once turned on, RY-RC are held on.
OFF: The status of RY-RC changes in real
ON : Once turned on, OUT-NO are held on.
OFF: The status of OUT-NO changes in real
Adjustment range
0.0 - fh (Hz)
0-255
[Hz]

0
G-9
E6581611
Action
time according to conditions.
time according to conditions.
Example of setting
2.5
4: LOW (Low-speed
detection signal)
Time [s]
ON
OFF
ON
OFF
7