When connecting to a communication board
C200HX
Communication
C200HG
board
C200HE
PLC
Communication
Model
*1
name
board
C200HW-COM02
C200HW-COM05
C200HW-COM06
C200HX
C200HG
*2
C200HE
C200HW-COM03
C200HW-COM06
*1
Product manufactured by OMRON Corporation. For details on the product, contact OMRON Corporation.
*2
The communication board cannot be mounted to the C2000HE-CPU11.
Use a host Link unit.
4 - 14
4. CONNECTION TO OMRON PLC
4.2 Serial Connection
Connection cable
Connection cable
Commun
Cable model
ication
Connection diagram number
Type
GT09-C30R20101-9P(3m)
or
RS-232
RS-232 connection
diagram 1)
GT09-C30R40101-9P(3m)
GT09-C100R40101-9P(10m)
GT09-C200R40101-9P(20m)
GT09-C300R40101-9P(30m)
RS-422
or
RS-422 connection
diagram 3)
GOT
GOT
Max.
Option device
distance
- (Built into GOT)
15m
GT15-RS2-9P
- (Built into GOT)
200m
GT15-RS4-9S
Communication driver
OMRON SYSMAC
Number of
connectable
Model
equipment
1 GOT for each port
of a communication
board