5.5 Temperature Controller Side Setting

POINT
POINT
POINT
OMRON temperature controller
For details of OMRON temperature controller, refer to
the following manual.
User's Manual of the OMRON temperature
controller
Model name
E5AN, E5EN, E5CN, E5GN
Temperature controller
E5ZN
Interface converter
K3SC-10
5.5.1
Connecting E5AN, E5EN,
E5CN, E5GN
Set the communication data by operating the key of the
temperature controller.
Item
Protocol
*1
Transmission speed
*1
Data bit
*1
Parity bit
*1
Stop bit
*2
Communication unit No.
*3
CMWT (Communications writing)
*1
Adjust the settings with GOT settings.
*2
Select the communication unit No. without overlapping with
that of other units.
*3
When changing the device values of the temperature
controller from the GOT, turn ON CMWT (Communications
writing) in advance.
5.5.2

Connecting E5ZN

Set the communication data by operating the key of the
temperature controller.
Item
*1
Transmission speed
*1
Data bit
*1
Parity bit
*1
Stop bit
*2
Communication unit No.
*3
CMWT (Communications writing)
*1
Adjust the settings with GOT settings.
*2
Select the communication unit No. without overlapping with
that of other units.
*3
When changing the device values of the temperature
controller from the GOT, turn ON CMWT (Communications
writing) in advance.
Refer to
5.5.1
5.5.2
5.5.3
Set value
CompoWay/F (Sysway)
9600bps, 19200bps
8 bits, 7 bits
Odd, Even, None
1bit, 2bits
0 to 99
ON
Set value
9600bps, 38400bps
8 bits, 7 bits
Odd, Even, None
1bit, 2bits
0 to 15
ON
5. CONNECTION TO OMRON TEMPERATURE CONTROLLER
5.5.3
Connection to interface
converter (K3SC-10)
Communication settings
Make the communication settings by operating the DIP
switch of the temperature controller.
Item
*1
19200bps, 38400bps
Transmission speed
*1
7 bits, 8 bits
Data bit
*1
Odd, Even, None
Parity bit
*1
1bit, 2bits
Stop bit
Communication Type
RS-232
*2
With, Without
Echo back
*1
Adjust the settings with GOT settings.
*2
Set to "Without".
Settings by DIP switch
Front of K3SC-10 body
Inside of K3SC-10 body
(When removing the front cover)
(1) Transmission speed settings
Switch No.
Transmission
speed (bps)
1
2
1200
ON
OFF
2400
OFF
ON
4800
ON
ON
9600
OFF
OFF
19200
ON
OFF
38400
OFF
ON

5.5 Temperature Controller Side Setting

Set value
RS485
Terminal block
for RS-422/485
communication
DIP switch
Terminal block
for RS-232
communication
3
Set these
switches.
OFF
OFF
OFF
OFF
ON
SW
ON
ON
5 - 13
5

Hide quick links:

Advertisement

Table of Contents
loading