Connecting To Dmc50; Connecting To Sdc45/46; Connecting To Cms, Cmf015; Connecting To Cml, Cmf050 - Mitsubishi Electric GOT2000 Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000:
Table of Contents

Advertisement

3.5.6

Connecting to DMC50

Communication settings
Make the communication settings by operating the
Smart Loader Package (SLP-D50/SLP-H21)of the
temperature controller.
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
Communication mode
CPL
Data bit
8bits (fixed)
Parity bit
Even (fixed)
Stop bit
1bit (fixed)
*2*3*4
0 to F
Module address
*1
Adjust the settings with GOT settings.
*2
Set the module address using the rotary switch for module
address.
*3
Do not set to "0".
*4
Select the module address without overlapping with that of
other units.
Module address setting
Set the module address using the rotary switch for
module address.
Rotary switch for the module address
3.5.7

Connecting to SDC45/46

Communication settings
Make the communication settings by operating the
Smart Loader Package (SLP-C45) of the temperature
controller.
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
*2
CPL
Communication mode
Data bit
7bits, 8bits
*1
Odd, even, none
Parity bit
Stop bit
1bit, 2bits
Communication minimum
1 to 250ms
*5
response time
*3*4
0 to 120
Station address
*1
Adjust the settings with GOT settings.
*2
Set to CPL.
*3
Do not set to "0".
*4
Select the station address without overlapping with that of
other units.
*5
When using the interface converter CMC10L, set the
communication minimum response time to 3ms or more.
Set value
Set value
3. CONNECTION TO AZBIL CONTROL EQUIPMENT
3.5.8

Connecting to CMS, CMF015

Communication settings
Make the communication settings by operating the key
of the control equipment.
Item
*1
9600bps
Transmission speed
0: 8-bit data length, Even parity, Stop bit 1
Communication condition
selection
1: 8-bit data length, Non parity, Stop bit 2
*2*3
0 to 99
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
3.5.9

Connecting to CML, CMF050

Communication settings
Make the communication settings by operating the key
of the control equipment.
Item
*1
9600bps
Transmission speed
00: 8-bit data length, Even parity, Stop bit 1
Communication condition
*1
selection
01: 8-bit data length, Non parity, Stop bit 2
*2*3
0 to 7F
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
3.5.10 Connecting to MQV
Communication settings
Make the communication settings by operating the key
of the control equipment.
Item
*1
9600bps, 19200bps, 38400bps
Transmission speed
00: 8-bit data length, Even parity, Stop bit 1
Communication condition
*1
selection
01: 8-bit data length, Non parity, Stop bit 2
*2*3
0 to 127
Station address
*1
Adjust the settings with GOT settings.
*2
Do not set to "0".
*3
Select the station address without overlapping with that of
other units.
3.5 Control Equipment Side Setting
Set value
3
Set value
Set value
3 - 53