■Intelligent function module number of MELSECNET/H remote I/O station
Intelligent function module number of MELSECNET/H remote I/O station is the upper 2 digits of the last number represented
with 3-digit number of the following "Input/output signal based on the remote I/O station".
Specify this with "Input/output signal based on the remote I/O station" regardless of the contents of common parameters set in
the master station of MELSECNET/H remote I/O network.
Input/output signal
based on the remote I/O station
Power supply
module
Remote I/O station,
station 1
Input/output signal
by common parameters
Read data, write data
The read buffer memory value is stored for reading, and the data to be written is stored for writing.
This function reads/writes data in byte unit.
■Data communication in ASCII code
Handle a word data for one buffer memory address as 2-byte data.
Convert the value to 2-digit (hexadecimal) ASCII code per one byte, and send it from the upper digit.
■Data communication in binary code
Handle a word data for one buffer memory address as 2-byte data.
Send 2-byte numerical values from lower byte (L: bits 0 to 7).
Ex.
When the data for one buffer memory address is 09C1H
ASCII code
C
1
0
9
43
30
39
31
H
H
H
H
When reading data from the following buffer memory addresses, 0H to 2H (additional value of the start address: 10000H)
Buffer memory
Address
Stored data
Word unit
0H
0003H
1H
0001H
2H
0012H
10 BUFFER MEMORY ACCESS
162
10.2 Intelligent Function Module
Y
Y
00 to
20 to
1F
2F
AJ72
Output
Output
Intelligent
LP25
module
module
32 points
16 points
32 points
Y
Y
400 to
420 to
41F
42F
Binary code
C1
09
H
H
Read 6 bytes from address 0H
Start
address
Byte unit
03H
10000H
00H
01H
00H
12H
00H
X/Y
Y
Y
30 to
50 to
70 to
4F
6F
8F
Output
Output
function
module
module
module
16 points
32 points
X/Y
Y
Y
430 to
450 to
470 to
44F
46F
48F
Read data (byte unit)
ASCII code
Binary code
30H, 33H
03H
30H, 30H
00H
30H, 31H
01H
30H, 30H
00H
31H, 32H
12H
30H, 30H
00H
Intelligent function module No. "04H"
Read 4 bytes from address 1H
Start
Read data (byte unit)
address
ASCII code
10002H
30H, 31H
30H, 30H
31H, 32H
30H, 30H
Binary code
01H
00H
12H
00H