■Extension specification modification
Specify the index register to be used when indexing the value specified by 'Extension specification'.
Access target
Devices
to be
used
MELSEC iQ-R
Index
series module
register
Long index
register
MELSEC-Q/L series
Index
module
register
Ex.
Index register (Z0)
Subcommand type
For MELSEC-Q/L series
For MELSEC iQ-R series
Ex.
Long index register (LZ0)
Subcommand type
For MELSEC iQ-R series
When do not perform index modification, specify '0'.
Subcommand type
For MELSEC-Q/L series
For MELSEC iQ-R series
■Device modification
Specify the number of index register when indexing device number.
The data to be specified is the same as extension specification modification. (Page 449 Extension specification
modification)
ASCII code
Device code
Device number
Specify 'Z' and
Specify the device number in decimal (2-
space with 2-digit
digit ASCII code).
ASCII code.
(Specification range: 0 to 24)
Specify 'LZ' with 2-
Specify the device number in decimal (2-
digit ASCII code.
digit ASCII code).
(Specification range: 0 to 12)
Specify 'Z' with 1-
Specify the device number in decimal (2-
digit ASCII code.
digit ASCII code).
(Specification range: 0 to 15)
ASCII code
Z
0
0
5A
30
30
H
H
H
Z
0
0
5A
20
30
30
H
H
H
H
ASCII code
L
Z
0
0
4C
5A
30
30
H
H
H
H
ASCII code
0
0
0
30
30
30
H
H
H
0
0
0
0
30
30
30
30
H
H
H
H
Binary code
Device number
Specify in hexadecimal.
(Specification range: 00H to 18H)
Specify in hexadecimal.
(Specification range: 00H to 0CH)
Specify in hexadecimal.
(Specification range: 0 to F)
Binary code
00
40
H
H
00
40
H
H
Binary code
00
80
H
H
Binary code
00
00
H
H
00
00
H
H
APPENDICES APPENDIX
Appendix 1 Read/Write by Device Extension Specification
Fixed
value
40H
80H
40H
A
449