Batch read (command: 0613)

Read data from the buffer memory of the host station (supported device).
Message format
The following shows the message format of the request data and response data of the command.
■Request data
Command
Subcommand
■Response data
The value read from the buffer memory is stored. The data order differs depending on the type of code, ASCII code or binary
code.
Page 154 Read data, write data
Data specified by request data
■Command
ASCII code
0
6
1
3
30
36
31
33
H
H
H
H
■Subcommand
ASCII code
0
0
0
0
30
30
30
30
H
H
H
H
■Start address
Specify the buffer memory start address to be read. (Page 153 Start address)
■Word length
Specify the word length of the buffer memory to be read. (Page 154 Word length)
Specification range: 1H to 1E0H (480)
Specify the access range within the range of buffer memory.
(Start address + Word length -1)  Buffer memory range
Start address
Word length
Binary code
13
06
H
H
Binary code
00
00
H
H
10 BUFFER MEMORY ACCESS
10.1 Buffer Memory
10
155