7.8 Channel Configuration

Fig. 7.10 Recording Channel Configuration

7.8.1 Recording Channel Setup

A – No Source
B – Analog Source
C – Digital Source
•1 If this parameter is changed from any previous setting other than 'None', a new internal data file for this
recording channel is created. All historical data stored internally for this channel is lost. If this parameter
is changed from a previous setting of 'None' new internal data files for all enabled recording channels
are created. Any unarchived data is lost.
IM/SM500F Rev. Z
Process Group 1,
Channels 1.1.to 1.6
•1
Select the signal source for the selected channel. This can be any external
analog or digital signal – see Appendix A, page 146 for full list.
Note.
•1
The input source for Channel 1 in any process group
analog source to ensure correct operation of the recorder.
•1
The tabs change according to the selection made.
Setting a channel source to 'None' does not switch off the analog
input to which the channel was assigned previously i.e. the analog
input continues to be monitored. To switch off an analog input, set
Analog I/P 'Type' for the required channel to 'Off' – see
Section 7.8.2, page 96.