Videographic Recorder
SM1000
4.6 Channel Configuration
Fig. 4.11 Recording Channel Configuration
4.6.1 Recording Channel Setup
A No Source
B Analog Source
C Digital Source
•1 If this parameter is changed from any previous setting other than 'None', a new internal data file for this recording channel is
created. All historical data stored internally for this channel is lost. If this parameter is changed from a previous setting of 'None'
new internal data files for all enabled recording channels are created. Any unarchived data is lost.
72
Process Group 1,
Channels 1.1 to 1.6
1
Select the signal source for the selected channel. This can be
any external analog or digital signal – see Appendix A, page 104
for full list.
Note.
The input source for Channel 1 in any process group
be an analog input to ensure correct operation of the
1
recorder.
The tabs change according to the selection made.
Setting a channel source to 'None' does not switch off the
analog input to which the channel was assigned
previously i.e. the analog input continues to be monitored.
1
To switch off an analog input, set Analog I/P 'Type' for the
required channel to 'Off' – see Section 4.6.2, page 74.
4 Configuration
must
IM/SM1000 Issue 11