Operating Mode Modbus Registers - ABB SM1000 User Manual

Videographic recorder
Hide thumbs Also See for SM1000:
Table of Contents

Advertisement

Videographic Recorder
SM1000
B.6 Operating Mode Modbus Registers
Tables B.13 to B.18 detail the contents of the Modbus registers
accessible while the instrument is in the operating mode.
Two data types are used:
32-bit single precision floating point data in IEEE format
64-bit double precision floating point data in IEEE format
Note.
When writing to a parameter that occupies more than
one register position then all registers relating to that
parameter MUST be written to as part of a multiple
register write. If this is not achieved a NAK exception
response is issued. Individual registers can be read
without causing an exception response.
When accessing a parameter that occupies more than
one register position, the lowest numbered register
contains the most significant data.
Analog Inputs
Read only, single precision floating point
A1
A2
A3
A4
A5
A6
B1
B2
B3
B4
B5
B6
Reserved
Table B.13 Analog Inputs
112
Modbus Registers
number –999 to +9999
0001 and 0002
0003 and 0004
0005 and 0006
0007 and 0008
0009 and 0010
0011 and 0012
0013 and 0014
0015 and 0016
0017 and 0018
0019 and 0020
0021 and 0022
0023 and 0024
0025 to 0100
Alarm Number and Name
1
Alarm 1.1A
2
Alarm 1.1B
3
Alarm 1.2A
4
Alarm 1.2B
5
Alarm 1.3A
6
Alarm 1.3B
7
Alarm 1.4A
8
Alarm 1.4B
9
Alarm 1.5A
10
Alarm 1.5B
11
Alarm 1.6A
12
Alarm 1.6B
13
Alarm 2.1A
14
Alarm 2.1B
15
Alarm 2.2A
16
Alarm 2.2B
17
Alarm 2.3A
18
Alarm 2.3B
19
Alarm 2.4A
20
Alarm 2.4B
21
Alarm 2.5A
22
Alarm 2.5B
23
Alarm 2.6A
24
Alarm 2.6B
Reserved
Table B.14 Alarm Trip Levels
Appendix B – Modbus Guide
Trip Point Registers
(single precision floating point)
Read: –999 to +9999
Write: –999 to +9999
0101 and 0102
0103 and 0104
0105 and 0106
0107 and 0108
0109 and 0110
0111 and 0112
0113 and 0114
0115 and 0116
0117 and 0118
0119 and 0120
0121 and 0122
0123 and 0124
0125 and 0126
0127 and 0128
0129 and 0130
0131 and 0132
0133 and 0134
0135 and 0136
0137 and 0138
0139 and 0140
0141 and 0142
0143 and 0144
0145 and 0146
0147 and 0148
0149 to 0250
IM/SM1000 Issue 11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents