Common Configuration; Setup - ABB SM1000 User Manual

Videographic recorder
Hide thumbs Also See for SM1000:
Table of Contents

Advertisement

Videographic Recorder
SM1000

4.4 Common Configuration

Fig. 4.8 Selecting Common Configuration

4.4.1 Setup

•1 If this parameter is changed, internally recorded data files are recreated and unarchived data is lost.
52
Configuration type is fixed as 'Basic'.
Enter the number of process groups required.
Each Process Group has 6 recording channels pre-assigned to
it – Group 1 (Ch1.1 to 1.6), Group 2 (Ch2.1 to 2.6).
If the Number of Groups is changed from 2 to 1, configuration
data for Process Group 2 is retained but not used.
Select the language to be used to display standard user
prompts and menu items.
Select a signal source used to acknowledge all active alarms in
both Process Groups simultaneously. Refer to Appendix A, page
104 for a description of the available sources.
Note. This signal is edge-triggered. A rising edge (inactive to
active) or falling edge (active to inactive) triggers global alarm
acknowledgement.
Enter the tag to be used to identify the instrument on
•1
configuration and audit log files.
Note. When reviewing data, the instrument tag is used to
identify the source of the data, therefore it is important to ensure
that the instrument tag is unique to each recorder.