Diagnosis
3.1 Diagnostics via LEDs
3.1.16
Terminal Module TM54F as of FW2.5 SP1
Table 3-18
Terminal Module TM54F - description of LEDs
LED
Color
READY
-
Green
Orange
Red
Green/red
Green/orange
or
Red/orange
L1+, L2+,
–
Red
L3+
–
Red
Fail-safe inputs / double inputs
F_DI z
LED
LED
(input x,
x
x+1
(x+1)+,
–
Red
(x+1)-)
–
–
–
Red
–
–
LED
LED
x
x+1
Green
Green
Green
Green
Inputs x+1 (DI 1+, 3+, .. 19+) can be set individually via parameter p10040.
1)
p10040 = 0: Input x+1 is NC contact.
p10040 = 1: Input x+1 is NO contact.
Factory setting: p10040 = 0 for all inputs x+1.
Single digital inputs, not fail-safe
DI x
–
Green
124
State
OFF
Electronics power supply is missing or outside permissible
tolerance range.
Continuous
The component is ready for operation and cyclic DRIVE-
CLiQ communication is taking place.
Continuous
DRIVE-CLiQ communication is being established.
Continuous
At least one fault is present in this component.
Note:
The LED is activated regardless of whether the
corresponding messages have been reconfigured.
Flashing
Firmware is being downloaded.
0.5 Hz
Flashing
Firmware download is complete. Wait for POWER ON
2 Hz
Flashing
Component recognition via LED is activated (p0154).
Note:
Both options depend on the LED status when component
recognition is activated via p0154 = 1.
ON
The controllable sensor power supply is functioning fault-
free.
Continuous
There is a fault in the controllable sensor power supply.
ON
Sensor power supply is functioning fault-free.
Continuous
There is a fault in the sensor power supply.
NC contact / NC contact
Continuous
Different signal states at input x and x+1
–
No signal at input x and no signal at input x+1
NC contact / NO contact
Continuous
Same signal states at input x and x+1
–
No signal at input x and a signal at input x+1
NC contact / NC contact
Continuous
A signal at input x and a signal at input x+1
NC contact / NO contact
Continuous
A signal at input x and no signal at input x+1
OFF
No signal at digital input x (x = 20..23)
Continuous
Signal at digital input x
Description, cause
: (z = 0..9, x = 0, 2, ..18)
1)
: (z = 0..9, x = 0, 2, ..18)
1)
: (z = 0..9, x = 0, 2, ..18)
1)
: (z = 0..9, x = 0, 2, ..18)
1)
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
Remedy
–
–
–
Remedy and
acknowledge
fault
–
Carry out a
POWER ON
–
–
–
–
–
–
–
Commissioning