Procedure
7.
p0300[0] = 283
8.
p0304[0] = ...
9.
p1900 = 1
Danger
During motor identification, the drive may cause the motor to move. The emergency STOP functions must
be fully operational during commissioning. To protect the machines and personnel, the relevant safety
regulations must be observed.
Commissioning
Commissioning Manual, (IH1), 07/2007 Edition, 6SL3097-2AF00-0BP7
2.8 Commissioning for the first time using as an example Vector AC DRIVE with BOP20
Motor type selection [MDS]*
0 No motor selected
Commissioning cannot be exited.
Standard motors:
1 Induction motor (rotating)
2 Synchronous motor (rotating, permanent-magnet)
5 Synchronous motor (rotating, separate field)
1x 1LAx standard induction motor (x = 1, 5, 6, 7, 8)
12 1LE2 standard induction motor (NEMA)
You must individually enter rated motor data (see type plate) in parameter
p0304 and onwards.
SIEMENS catalog motors:
10x 1PHx induction motor (x = 2, 4, 7)
13x 1PMx induction motor (x = 4, 6)
2xx Synchronous motors
The listed motors appear in a motor code list (see SINAMICS S List
Manual (LH1)). You can select the motor by entering the motor type
(p0300) and the motor code number (p0301). The parameter for the rated
motor data (p0304 and onwards) are pre-assigned accordingly.
Rated motor data [MDS]
Only when p0300 < 100 (third-party motor)
Enter the rated motor data in accordance with the type plate, e.g.
p0304[0] Rated motor voltage [MDS]
p0305[0] Rated motor current [MDS]
p0307[0] Rated motor output [MDS]
p0308[0] Rated motor power factor [MDS] (only when p0100 = 0)
p0309[0] Rated motor efficiency [MDS] (only when p0100 = 1)
p0310[0] Rated motor frequency [MDS]
p0311[0] Rated motor speed [MDS]
p0335[0] Motor cooling type [MDS] *
0: Natural cooling
1: Forced cooling
2 Water cooling
Motor data identification and rotating measurement *
0 Inhibited
1 Motor data identification for rotating motor
2 Motor data identification at standstill
Alarms A07980 and A01991 are output.
Description
Commissioning
Factory
setting
0
-
2
83