Fault tracing
What this chapter contains
This chapter describes the fault tracing of the line-side converter. For motor-side
converter fault tracing, see the appropriate application program firmware manual.
Faults and warnings displayed by the CDP-312R Control Panel
The control panel will display the warnings and faults of the unit (i.e. line-side
converter or motor-side converter) the panel is currently controlling.
Information on warnings and faults concerning the line-side converter are contained
within the IGBT Supply Control Program Firmware Manual [3AFE68315735
(English)].
The warnings and faults concerning the motor-side converter are dealt with in the
application program (e.g. Standard Application Program) Firmware Manual.
Warning/Fault message from unit not being monitored by control panel
Flashing messages WARNING, ID:2 or FAULT, ID:2 on the control panel display
indicate a warning or fault state in the line-side converter when the panel is
controlling the motor-side converter:
FAULT, ID:2
ACS 800 0490_3MR
*** FAULT ***
LINE CONV
To display the warning or fault identification text, switch the control panel to view the
line-side converter as described in section
Conflicting ID numbers
If the ID numbers of the line-side and the motor-side converters are set equal, the
control panel stops functioning. To clear the situation:
• Disconnect the panel cable from the RMIO board of the motor-side converter.
• Set the ID number of the line-side converter RMIO board to 2. For the setting
procedure, see the application program (e.g. Standard Application Program)
Firmware Manual.
• Connect the disconnected cable to the RMIO board of the motor-side converter
again and set the ID number to 1.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com